Question:
Re: CQD answer published Tuesday, January 10, 2017 -
Hi Charlie,
In the answer you gave about the air-conditioning being supplied from the same panel as the elevator you said that air conditioners are not emergency loads. Would that be a problem if it was supplied from the same panel?
Jerrod
A
Answer:
Hey Jerrod thanks for your follow up question. Yes it would be a problem because emergency systems can supply other loads as stated in 700.4(B) but separate transfer equipment is required as stated in 700.5(D) which would likely result in using multiple panelboards or other type of distribution equipment.