Question:
Article 590.4(H) allows flexible cords and cables to pass through doorways or other pinch points. Does it also allow them to run through holes in walls?
Craig Schumann
A
Answer:
Hey Craig thanks for your question. No, 590.4(H) does not specifically state that flexible cords can be run through holes in walls to modify the rule in 400.12(2). Check with the AHJ to see if they will allow the flexible cord to be run through a hole if it is not exposed to physical damage for your particular application.