Thursday, December 1, 2016
Question:
Can you run landscape wiring thru a house?
Al Lamke
A
Answer:
Hey Al thanks for your question. Yes, if the appropriate wiring is used. The secondary circuit conductors must meet the provisions of 411.6(D) and must use one of the wiring methods of Chapter 3 unless supplied by Class 2 power sources. If the power source is Class 2 then the cables must comply with Article 725, specifically 725.130 and 725. 179. Keep in mind the lighting operating at 30 volts or less must be listed as stated in 411.4 and follow all instructions included as part of that listing based on 110.3(B).