Question:
Happy Friday CQD,
Are junction and pull boxes required to have minimum working spaces that appear in Section 110.26?
Barry Turner
A
Answer:
Hi Barry,
Thanks for the question. This one on the surface is an easy one to respond to. The answer is no. Minimum working spaces addressed in Section 110.26 are intended to apply to equipment that is likely to be serviced while energized. Junction and pull boxes generally do not fall in this category, but they are required to be accessible (as applied to wiring methods) based on the definition in Article 100.