Monday, April 18, 2022
Question:
Good Morning,
Can I use standard, multi-neutral MC cable to a given area, above ceiling, before using HCF-rated MC cable to feed patient care areas?
Michael Funfar
A
Answer:
Greetings Michael,
Thanks for the question. Based on the information provided the standard multi-neutral MC cable could be run in areas that are not patient care spaces. Not all MC cable is suitable for use in patient care spaces. See Section 517.13(A) and (B) for the full requirements. The project specifications and local Code rules may also apply to your situation.