Wednesday, May 20, 2020
Question:
Hello CQD,
Is it ok to use FMC behind Sheetrock on a concrete wall to an outlet? The concrete wall has 3/4 inch furring strips.
Scott Bosch
A
Answer:
Hi Scott,
Thanks for the question. The uses permitted for flexible metal conduit are addressed in Section 348.10, which indicates that FMC shall be permitted to be installed in exposed and concealed locations. Section 348.12 provides uses not permitted for FMC, which are not mentioned in the question.