Question:
How does the GFCI protection requirement for receptacles within 6 feet of a sink apply to the new washing machines that have built in sinks?
Mike Dowdy
A
Answer:
Hey Mike thanks for your question. It seems the rule applies the same way as for any other sink.
All 125-volt, 15- and 20-ampere receptacles within 6 ft of the top inside edge of the sink bowl in dwelling units must have GFCI protection as stated in 210.8(A)(7).