Friday, July 1, 2016
Question:
Referring to Table 220.42, after deducting the first 3,000VA from the calculated load, do you then subtract an additional 3,000Va from the 120,000VA limit set forth in the table?
Chuck Whitaker
A
Answer:
Hey Chuck thanks for your question. Yes, the first 3000 VA is at 100%, the next 117, 000% (3001 to 120,000) is at 35%, and the remainder is at 25%. The example in Annex D, - D4(a) Multifamily Dwelling confirms this.