Question:
I want to interlock two cooling systems to reduce the loads in sizing the service. What article is appropriate to review? Is this done?
Jim Cowles
A
Answer:
Hey Jim thanks for your question. Possibly you are thinking about 220.60 for noncoincedent loads. This section is commonly used to compare the air conditioning and heating load and use the larger as they would not be both used at the same time.