Friday, August 12, 2016
Question:
Re: CQD answer published Friday, June 24, 2016 - GFI protection for basement sump pump receptacle 2
Perhaps you should reread 400.7(B) as it is not a violation of several sections of 400.7(A) such a s for elimination of vibration from a pump motor.
Cordially, Bill Nolte, C.S.H.O.
A
Answer:
Hey Bill thanks for your comment. I did and you make a good point- if the cord was used to deal with a noise or vibration issue then an attachment plug is not required as 400.7(A)(7) is not referenced in 400.7(B). Thanks for the correction.