Question:
Is so hard usage cable allowed to be run in cable tray. 3phase system.
Edward Lohutko
A
Answer:
Hey Edward thanks for your question. The wiring methods allowed in cable trays are provided in Table 392.10(A). If you mean hard usage flexible cord, those are not included in that table. It would also not comply with 400.12(1).