Question:
Are you permitted to install a circuit using surface metal raceway (like Wiremold) under a raised floor in a data processing area?
A
Answer:
Yep, section 645-5(d)(2) says 'The branch-circuit supply conductors to receptacles or field-wired equipment are in ... surface metal raceway with metal cover ...'