Question:
Good afternoon,
I am remodeling my house and wanted to know per NEC 2014, Can I use 1/2" metallic liquid Tight conduit for runs longer than 6' if, I pulled a dedicated ground wire.
Thank you,
Brad Everett
A
Answer:
Hi Brad,
Thanks for participating. The six-foot limitation applies where the LFMC is being installed and being used as an equipment grounding conductor as provided in 250.118(6) and to comply generally with Section 356.12(3). That said, Section 356.12(3) refers to 356.10(5) meeting the requirements in 356.10(5), which recognized lengths longer than 6 feet and meets the securement provisions in accordance with 356.30.