Tuesday, December 28, 2021
Question:
Hello NEC Friends,
I was hoping you could help settle a difference of opinion in our office. If a raceway (EMT) is installed on the side of a building, is the interior of the raceway considered a wet location?
Adam Parks
A
Answer:
Hi Adam,
Section 300.9 of the NEC indicates that where raceways are installed in wet locations above grade, the interior of these raceways shall be considered to be a wet location. Insulated conductors and cables installed in raceways in wet locations above grade shall comply with 310.10(C).