Thursday, December 6, 2018
Question:
Question 1) does pvc underground conduit need to be spaced apart. If it does what is the code article. 2) what is the meaning of 310.15(3)(b)
Jim Churilla
A
Answer:
Hey Jim thanks for your question. Yes, spacing between raceways is required, as you mention, as stated in 310.15(B)(3)(b). That is the section subdivision reference. No specific dimension is provided for the spacing but the spacing achieved by fittings and support means is generally accepted.