Question:
Hello, I have a temporary power pole and the inspector just red tagged my installation and stated that I cannot terminate two grounding electrode conductors to a ground rod using the same, single grounding clamp. Is this a violation of the Code, if so, what section applies.
Thanks,
Issac Small
A
Answer:
Hi Issac, the NEC does address that type of installation. The Code generally would restrict using a single grounding clamp for one conductor, unless the clamp is listed for multiple conductors. See Section 250.70.