Tuesday, August 20, 2019
Question:
Hi, We are building a medical office in New Jersey and wanted to ask if we need hospital grade wiring. It is a basic care space where only minor procedures and examinations will be performed in this office.
Thank you. Joseph
A
Answer:
Hey Joseph thanks for your question. Yes. Patient Care Space, as that term is defined in 517.2, must use the wiring methods in 518.13(A) and have insulted equipment grounding conductors in 518.13(B) as stated in 517.13.