Friday, July 28, 2023
Question:
Hi Charlie, thanks for providing this forum. Is a 2-pole GFCI breaker required for a dwelling unit air conditioning condensing unit? Thank You, Jim Stevens
A
Answer:
Hello Jim, glad you are enjoying the CQD. As of this writing, HVAC equipment is excluded from the requirements of Section 210.8(F) as
Exception No. 2 delays the application of GFCI protection for dwelling unit, listed, HVAC equipment until September 1, 2026.