Question:
Re: CQD answer published Thursday, October 27, 2016 -
I’m not sure I agree with your response to Wednesday October 26th question.
501.135 (B) (2) has an exception to (2) allowing electrical resistance heat tracing identified for Class 1, Division 2.
Mark Briels
A
Answer:
Hey Mark thanks for your comment. Exception No 2 refers to 501.135(B)(2), all part of (B) for C1D2 locations. The original question asked if C1D2 equipment could be used in C1D1 locations, 501.135(A).