National Electrical Installation Standards

Standards as High as Your Own

 

Featured Standards

neca416cover_web

NECA 416-2016 Recommended Practice for Installing Energy Storage Systems

This standard describes methods and procedures used for installing multiple types energy storage systems. It also includes information about controlling and managing energy storage systems, in addition to commissioning and maintaining energy storage systems.
» Learn More
NECA301-16Cover_WEB

NECA/FOA 301-2016 Standard for Installing and Testing Fiber Optics

This standard describes installation and test procedures for fiber optic cabling networks. This standard applies fiber optic cabling installed indoors (premises installations) and outside plant (OSP) applications.
» Learn More

State Regulationsusa country shape

Find the major provisions of electrical code, enforcement, and contractor/electrician licensing requirements for each state in the U.S.

US Electrical Codes & Regulations by State »
Licensing Information by State ».

NEC Adoption by State

Building Codes Assistance Project Energy Code Adoption

Code Question of the Daytextbook

  • Wednesday, October 17, 2018
    CQD: 10/17/2018

    Charlie, Thank you for your service...enjoyable and very informative. Section 300.3(B) discusses conductors of the same circuit and in general, requires that all conductors (including the grounded conductor and all equipment grounding conductors and bonding conductors) to be contained within the same raceway, auxiliary gutter, cable tray, cablebus assembly, trench, cable, or cord unless otherwise permitted in accordance with 300.3(B)(1) through (B)(4). An exception under 300.3(B)(1) - Parallel Installations - allows conductors that are installed in underground, non-metallic raceways to be arranged as isolated phase installations as long as the raceways are installed in close proximity and comply with 300.20(B). Section 300.5(I) discusses conductors of the same circuit in underground installations. This section also requires all conductors of the same circuit (including the grounded conductor and all equipment grounding conductors) to be installed in the same raceway or cable "or shall be in close proximity in the same trench." Exception No. 2 under this section, however, allows isolated phase, polarity, grounded conductor, and equipment grounding and bonding conductor installations in non-metallic raceways in close proximity where conductors are paralleled as permitted in 310.10(H), and where the conditions of 300.20(B) are met.

    Now to my question: For an underground 3 phase, 5 wire installation (3 phase conductors, an equipment grounding conductor, and a grounded conductor), can the 3 phase wires and the equipment grounding conductor be installed together in a single underground PVC conduit and the grounded conductor be installed in a separate, adjacent underground PVC conduit? The conductors are "installed in close proximity in the same trench" per the last sentence of Section 300.5(I) and this also appears to meet the general intent covered by Exception No. 2 under Section 300.5(I). However, this is not a parallel installation and each phase is not isolated. All phase conductors (and the equipment grounding conductor) are grouped together in one underground PVC conduit and the grounded conductor (the neutral) is installed in a separate underground PVC conduit with both conduits being side by side (i.e. in close proximity in the same trench). Thanks, Chris DeWeese

  • Tuesday, October 16, 2018
    CQD: 10/16/2018
    View Question and Answer

How's your knowledge?
» Get the Answer!